Input method: three-phase+N-wire+ground wire
Rated AC input: 380/400/415VACVoltage range: -40%- 20% can be set
Rated frequency: 50/60Hz
Frequency range: 50/60Hz10%, 2.5%, 5%, 10%, 20% can be set)
Output method: three-phase+N-wire+ground wire
Rated AC input: 208/220/230/240VAC
Voltage normal state: consistent with mains power
Voltage emergency state: 380/400/415VAC (adjustable within 5%)
Frequency normal state: consistent with mains power
Frequency emergency state: 50/60Hz 0.05%
Switching time:<5ms
4. ChargerOutput voltage: 405VDC (default, can be automatically adjusted according to battery configuration and status)
Charging voltage and current: can be adjusted according to the on-site battery configuration
5. InverterVoltage stabilization accuracy: 1% (100% balanced negative cutoff), 2% (100% unbalanced negative cutoff)
Voltage dynamic transient: 5% (0-100% load variation)
Total harmonic voltage distortion:<1% (100% linear load)
Voltage dynamic response time:<5m
sInverter overload capacity: 125% for 10 minutes, 150% for 1 minute
Frequency accuracy: 0.05%
Waveform: Pure sine wave
Optional SNMP card: supports remote monitoring and management through a network browser managed by SNMP
Note: Special requirements can be customized, and product parameters are subject to change without prior notice
The technical specifications of HB-E6000 series 100-400 KW EPS emergency power supply are as follows:
Rated AC input: 380/400/415VAC
Voltage range: -40% -20% can be set
Frequency range: 50/60Hz (10%, 2.5%, 5%, 10%, 20% can be set)
4. Charger
Output voltage: 432VDC (default, can be automatically adjusted according to battery configuration and status)
Charging voltage and current:
can be adjusted according to the on-site battery configuration
Total harmonic voltage distortion:<1% (100% linear load),<3% (100% nonlinear load)